Technical Indicators
  • Ingress Protection: IP65 certified.
  • Accuracy Class: 1.0 at +20°C and 2.5 between -20 to +60°C.
  • Measurement Range: Supports -0.1 to 0.5 MPa and -0.1 to 0.9 MPa.
  • Ambient Temperature: Standard -20 to +60°C, with low-temp options for -40°C and -50°C.
  • Anti-vibration: Resists up to 20 m/s².
  • Anti-impact: 500 m/s² for liquid-filled (FZ) and 300 m/s² for standard (F).
  • Leakage Rate: Maximum permissible rate is 1 × 10⁻⁹ Pa⋅m³/s.
Contact Signal
  • Contact Type: Electric contact design.
  • Contact Capacity: Rated for 30W / 50VAC with a maximum current (\(I_{\max }\)) of 1A.
  • Insulation Performance: Built for 2kV at 50Hz and insulation resistance ≥ 100MΩ.
  • Contact Resistance: Kept strictly ≤ 0.5Ω.
Communication Signal
  • Working Voltage: Operates on DC24V.
  • Communication Mode: Supports 4 ~ 20mA (01) or RS485 (02).
  • Communication Protocol: Utilizes ModBus (02).
  • EMC Standards:
    • IEC 61000-4-2 (ESD): Level 4 (8kV / 15kV)
    • IEC 61000-4-3 (Field): Level 4 (30V/m)
    • IEC 61000-4-4 (Burst): Level 4 (± 4kV)
    • IEC 61000-4-5 (Surge): Level 4 (± 4kV)
    • IEC 61000-4-8 (EMC): Level 5 (100A/m)
Rating Pressure and Set Point
  • Standard Temperature: +20°C is used to represent standard SF₆ gas density values.

Additional information

Material

Stainless Steel

Condition

New

Brand

TONE